In response to the recent rise in cyber threat due to the Russian-Ukraine crisis, NetApp is actively monitoring the global security intelligence and updating our cybersecurity measures. We follow U.S. Federal Government guidance and remain on high alert. Customers are encouraged to monitor the Cybersecurity and Infrastructure Security (CISA) website for new information as it develops and remain on high alert.

過熱後に ATTO FibreBridge に到達できません

Views:
28
Visibility:
Public
Votes:
0
Category:
metrocluster
Specialty:
metrocluster
Last Updated:

に適用されます

ATTO 6500N
ATTO 7500N
ATTO 7600N
MetroCluster
の過熱
ログ・メッセージログ・メッセージ
 1D0AA8 00:36:43 WARN Temperature Critical Level reached at 71 C
 1D0AA9 00:36:45 CRIT Temperature (71 C) out-of-range (0, 70 C). Going offline.

問題

ATTO ブリッジが削除済みとして報告され、次のようなエラーメッセージが報告されます。
Sat Feb  4 16:06:38 CET [netapp01:bridge.removed:info]: FC-to-SAS bridge sw2:5.125L0 [ATTO     FibreBridge6500N 1.11] S/N [FB6500N123456] was removed.

 

 

 

 