SwitchPowerFail_Alert」および"SwitchPsuFanNotOperational_Alert"がクラスタネットワークスイッチで報告されており、PowerSupplyを指しています
::> system health subsystem show
Subsystem Health
----------------- ------------------
SAS-connect ok
Environment ok
Memory ok
Service-Processor ok
Switch-Health degraded
CIFS-NDO ok
Motherboard ok
IO ok
MetroCluster ok
MetroCluster_Node ok
FHM-Switch ok
FHM-Bridge ok
SAS-connect_Cluster ok
13 entries were displayed.::> system health alert showNode: Node-n09Alert ID: SwitchPowerFail_AlertResource: PowerSupply-1Severity: MajorIndication Time: Mon Oct 27 17:23:14 2025Suppress: falseAcknowledge: falseProbable Cause: "PowerSupply-1" on switch"switch1(FOCXXXXXXXX)" is missing or isnot operational.Possible Effect: Power supply redundancy on switch"switch1(FOCXXXXXXX)" might be lost.Corrective Actions: 1) Ensure that the power supply units supplying power to the switch are turned on.2) Ensure that the power cord is securely connected tothe power supply of the switch.Node: Node-n09Alert ID: SwitchPowerFail_AlertResource: PowerSupply-1Severity: MajorIndication Time: Mon Oct 27 17:23:14 2025Suppress: falseAcknowledge: falseProbable Cause: "PowerSupply-1" on switch"switch2(FOCYYYYYYYY)" is missing or isnot operational.Possible Effect: Power supply redundancy on switch"switch2(FOCYYYYYYY)" might be lost.Corrective Actions: 1) Ensure that the power supply units supplying power to the switch are turned on.2) Ensure that the power cord is securely connected tothe power supply of the switch.Node DR-A900-MCC-02Monitor: ethernet-switchAlert ID: SwitchPsuFanNotOperational_AlertAlerting Resource: DR-MCC-SW01(FLM2814034Z)/PowerSupply-2 Fan-1Subsystem: Switch-HealthIndication Time: Wed Jun 24 02:04:17 2026Perceived Severity: MajorProbable Cause: Out_of_serviceDescription: "PowerSupply-2 Fan-1" on switch "DR-MCC-SW01(FLM2814034Z)" is not functioning properly.Corrective Actions 1) Use the switch CLI to verify that the fan is functioning at the expected speed. 2) Replace the fan, if it is not operational.Possible Effect Cooling of switch "DR-MCC-SW01(FLM2814034Z)" might be degraded.Acknowledge FALSESuppress FALSEPolicy SwitchPsuFanNotOperational_PolicyAcknowledgerSuppressorAdditional Information Switch Name: DR-MCC-SW01(FLM2814034Z) Switch Show Model: N9K-C9336C-FX2 Switch Serial Number: FLM2814034Z Fan Name: PowerSupply-2 Fan-1 Single Fan or Fan Tray: single Is PSU Fan: yes Fan Container Name: PowerSupply-2 Fan Status: not-operational Successive Warning Count: 943 Error Description: operStatus=3 Switch Fan Resource Status: okAlerting Resource Name DR-MCC-SW01(FLM2814034Z)/PowerSupply-2 Fan-1- EMSログ:
Thu Oct 23, 2025 04:03:17 +0000 HA Group Notification (Health Monitor process cshm: SwitchPowerFail_Alert[switch1(FOCXXXXXX)/PowerSupply-1]) ALERTThu Oct 23, 2025 04:03:17 +0000 HA Group Notification (Health Monitor process cshm: SwitchPowerFail_Alert[switch2(FOCYYYYYY)/PowerSupply-1]) ALERT::> system switch ethernet power show Admin OperationalSwitch Power Supply Status Status Error------------------ ----------------- ---------- ----------- ---------------Switch1 PowerSupply-1 on failed offEnvPowerSwitch1 PowerSupply-2 on operationalSwitch2 PowerSupply-1 on failed offEnvPowerSwitch2 PowerSupply-2 on operational- スイッチからの「
show env」出力では、次の内容が報告されます:
switch1# show env
Fan:
---------------------------------------------------------------------------
Fan Model Hw Direction Status
---------------------------------------------------------------------------
Fan1(sys_fan1) NXA-FAN-30CFM-F -- back-to-front Ok
Fan2(sys_fan2) NXA-FAN-30CFM-F -- back-to-front Ok
Fan3(sys_fan3) NXA-FAN-30CFM-F -- back-to-front Ok
Fan4(sys_fan4) NXA-FAN-30CFM-F -- back-to-front Ok
Fan_in_PS1 -- -- back-to-front Shutdown
Fan_in_PS2 -- -- back-to-front Ok
Fan Zone Speed: Zone 1: 0x9a
Fan Air Filter : NotSupported
Power Supply:
Voltage: 12 Volts
Power Actual Actual Total
Supply Model Output Input Capacity Status
(Watts ) (Watts ) (Watts )
------- ---------- --------------- ------ ---------- --------------------
1 NXA-PAC-650W-PE 0 W 0 W 0 W Shutdown
2 NXA-PAC-650W-PE 99 W 110 W 650 W Ok
switch2# show env
Fan:
---------------------------------------------------------------------------
Fan Model Hw Direction Status
---------------------------------------------------------------------------
Fan1(sys_fan1) NXA-FAN-30CFM-F -- back-to-front Ok
Fan2(sys_fan2) NXA-FAN-30CFM-F -- back-to-front Ok
Fan3(sys_fan3) NXA-FAN-30CFM-F -- back-to-front Ok
Fan4(sys_fan4) NXA-FAN-30CFM-F -- back-to-front Ok
Fan_in_PS1 -- -- back-to-front Shutdown
Fan_in_PS2 -- -- back-to-front Ok
Fan Zone Speed: Zone 1: 0x9a
Fan Air Filter : NotSupported
Power Supply:
Voltage: 12 Volts
Power Actual Actual Total
Supply Model Output Input Capacity Status
(Watts ) (Watts ) (Watts )
------- ---------- --------------- ------ ---------- --------------------
1 NXA-PAC-650W-PE 0 W 0 W 0 W Shutdown
2 NXA-PAC-650W-PE 98 W 108 W 650 W Ok