問題

パートナーノードで自動テイクオーバーが実行されました。
 
EMSログ
  • パートナー ノード
callhome.sfo.takeover:alert]: Call home for CONTROLLER TAKEOVER COMPLETE AUTOMATIC
cf_takeover: callhome.reboot.takeover:notice]: Call home for PARTNER REBOOT (CONTROLLER TAKEOVER)
cf_takeover: cf.fm.takeoverComplete:notice]: Failover monitor: takeover completed
  • 影響を受けるノード(リブート後)

splog_main: mgr.boot.reason_abnormal:EMERGENCY]: System rebooted due to a power glitch.

splog_main: callhome.reboot.glitch:notice]: Call home for REBOOT (power glitch)

 シェルフに電源障害も報告されている

cf_hwassist: cf.hwassist.takeoverTrapRecv:notice]: hw_assist: Received takeover hw_assist alert from partner(cluster1-01), system_down because power_loss.
dsa_worker5: ses.status.psWarning:error]: DS224-12 (S/N SHF#############) shelf 0 on channel 7a power warning for Power supply 2: warning status; DC undervoltage. This module is on the rear of the shelf at the bottom right.
dsa_worker4: ses.status.psWarning:error]: DS224-12 (S/N SHF#############) shelf 10 on channel 9d power warning for Power supply 2: warning status; DC undervoltage. This module is on the rear of the shelf at the bottom right.

SPイベントログ

Record 589: Fri Aug 06 19:01:37.000000 2021 [SP.emergency]: System input power lost
Record 590: Thu Jan 01 00:00:49.400961 1970 [IPMI.notice]: 7204 | c0 | OEM: ffff7000ff00 | ManufId: 150300 | SP Power Reset
Record 591: Thu Jan 01 00:00:49.450536 1970 [IPMI.notice]: 7304 | c0 | OEM: fcff70560000 | ManufId: 150300 | POS Register: Power on Reset(Normal Power Cycle)

Record 407: Fri Feb 28 03:34:17.489482 2020 [Agent.notice]: 127.880: 3 : AC Power Loss Signal PSU1 de-asserted
Record 408: Fri Feb 28 03:34:17.489664 2020 [Agent.notice]: 128.100: 4 : AC Power Loss Signal PSU2 de-asserted
Record 409: Fri Feb 28 03:34:17.557708 2020 [Agent.notice]: 196.145: 4 : AC Power Loss Signal PSU2 asserted
Record 410: Fri Feb 28 03:34:17.570049 2020 [Agent.notice]: 208.526: 3 : AC Power Loss Signal PSU1 asserted
Record 411: Fri Feb 28 03:34:17.635848 2020 [Agent.notice]: 274.301: 14 : Attention LED (at Midplane) asserted
Record 412: Fri Feb 28 03:34:23.431854 2020 [Agent.notice]: 070.290: 14 : Attention LED (at Midplane) de-asserted
Record 413: Fri Feb 28 03:34:27.516634 2020 [SP.warning]: AC_OK Low Detected
Record 419: Fri Feb 28 03:39:47.942198 2020 [SP.critical]: Filer Reboots

Sign in to view the entire content of this KB article.

New to NetApp?

Learn more about our award-winning Support

NetApp provides no representations or warranties regarding the accuracy or reliability or serviceability of any information or recommendations provided in this publication or with respect to any results that may be obtained by the use of the information or observance of any recommendations provided herein. The information in this document is distributed AS IS and the use of this information or the implementation of any recommendations or techniques herein is a customer's responsibility and depends on the customer's ability to evaluate and integrate them into the customer's operational environment. This document and the information contained herein may be used solely in connection with the NetApp products discussed in this document.