BESスイッチが電源喪失、ファン、およびPSUエラーで再起動し続ける
環境
- BES-53248クラスタネットワークスイッチ
問題
- BESスイッチが突然リブートし続けると、スイッチのイベントログに次のエラーが記録される
<185> Dec 3 20:30:26 0.0.0.0-1 SIM[Cnfgr_Thread_]: sim_util.c(4233) 25 %% ALRT Switch was reset due to power disruption or unexpected restart.(error[0x0]).
<188> Dec 3 15:31:27 cs1-1 BOXSERV[boxs_Req]: boxs.c(1671) 19305 %% WARN Unit 1 power supply 1 POWER LOSS event (5) occurred.
<187> Dec 3 15:31:39 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19308 %% ERR Unit 1 fan 7 FAILURE event (4) occurred.
<187> Dec 3 15:49:01 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19316 %% ERR Unit 1 fan 11 FAILURE event (4) occurred.
<187> Dec 3 15:49:58 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19320 %% ERR Unit 1 fan 1 FAILURE event (4) occurred.
<187> Dec 3 17:09:54 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19327 %% ERR Unit 1 fan 11 FAILURE event (4) occurred.
<187> Dec 3 17:11:25 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19331 %% ERR Unit 1 fan 6 FAILURE event (4) occurred.
<188> Dec 3 17:48:03 cs1-1 BOXSERV[boxs_Req]: boxs.c(1671) 19336 %% WARN Unit 1 power supply 1 POWER LOSS event (5) occurred.
<187> Dec 3 17:50:20 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19340 %% ERR Unit 1 fan 3 FAILURE event (4) occurred.
<187> Dec 3 20:13:07 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19346 %% ERR Unit 1 fan 8 FAILURE event (4) occurred.
<187> Dec 3 20:14:55 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19350 %% ERR Unit 1 fan 3 FAILURE event (4) occurred.
<187> Dec 3 20:15:05 cs1-1 BOXSERV[boxs_Req]: boxs.c(1584) 19354 %% ERR Unit 1 fan 12 FAILURE event (4) occurred.
<188> Dec 3 20:15:56 cs1-1 BOXSERV[boxs_Req]: boxs.c(1671) 19358 %% WARN Unit 1 power supply 2 POWER LOSS event (5) occurred.
- クラスタまたはデータセンター内の他のデバイスに既知の電源の問題はありません。