「Power Fail」エラーが原因でノードがリブートします
環境
- AFF - A300 / FAS8200または FAS2620 / FAS2650
- FAS2720 / FAS2750
- AFF-A220
問題
- ノードコンソールまたは
SP/BMC> system log
の出力に、「Power Fail」エラーが原因でノードがリブートすることが表示されます。
例 (reboot):
****************************
* Power Fail - Please Wait *
****************************
...
Destage is in progress, please wait
..........................................
Destage is completed successfully
Powering off from the backup power source
:
Waiting for giveback...(Press Ctrl-C to abort wait)
例 (ブートループ):
****************************
* Power Fail - Please Wait *
****************************
...
Destage is in progress, please wait
..........................................
Destage is completed successfully
Powering off from the backup power source
BIOS Version: 11.2.1
Portions Copyright (C) 2014-2018 NetApp, Inc. All Rights Reserved.
...
Initializing System Memory ...
Loading Device Drivers ...
BIOS Version: 11.2.1
Portions Copyright (C) 2014-2018 NetApp, Inc. All Rights Reserved.
Initializing System Memory ...
Loading Device Drivers ...
- ノード
SP/BMC events all
のレポート:
Record 1234: Mon Jan 1 00:01:01 2024 [SP.emergency]: System input power lost
Record 2345: Mon Jan 1 00:10:10 2024 [SP.emergency]: System input power lost
- Power Supply Unit(PSU;電源装置ユニット) 、Power Distribution Unit(PDU;配電ユニット )、またはその他のデータセンターの電気的要素(シェルフ、スイッチなど)からは、その他の電源アラートは報告されません。