メインコンテンツまでスキップ

シェルフ冷却ユニットに障害が発生しました

Views:
7
Visibility:
Public
Votes:
0
Category:
disk-shelves
Specialty:
HW
Last Updated:

環境

  • AFFシステム
  • FASシステム
  • ストレージ シェルフ

問題

ファン がCriticalを報告する例

  • DS460C

Wed Mar 09 11:43:31 -0500 [NODE03: dsa_worker4: ses.status.fanError:EMERGENCY]: DS460-12 (S/N SHJGXXXXXXXX) shelf 1 on channel 0a cooling fan error for Cooling element 3: critical status; fan is off. This module is on the rear of the shelf to the left.

Wed Mar 09 11:43:31 -0500 [NODE03: dsa_worker4: callhome.shlf.fan:EMERGENCY]: Call home for SHELF COOLING UNIT FAILED
 
Wed Mar 09 11:43:40 -0500 [NODE04: statd: monitor.shelf.fault:alert]: Critical fault reported on disk storage shelf attached to channel 0a. Check fans, power supplies, disks, and temperature sensors.
Wed Mar 09 11:43:40 -0500 [NODE04: statd: callhome.shlf.fault:error]: Call home for SHELF_FAULT

NS224:BR

Mon Mar 14 09:13:52 +0900 [Node01: dsa_worker1: ses.status.fanError:EMERGENCY]: NS224NSM100 (S/N SHFNxxxxxx) shelf 0 on channel 0x cooling fan error for Cooling element 15: critical status; fan is off. This element is on the unknown location.

Mon Mar 14 09:13:52 +0900 [Node01: dsa_worker1: callhome.shlf.fan:EMERGENCY]: Call home for SHELF COOLING UNIT FAILED

  •   DS2246 

Wed Mar 13 14:57:10 +0530 [rpsdlxx1: dsa_worker4: ses.status.temperatureInfo:info]: DS2246 (S/N SHFFG1451000046) shelf 12 on channel 0a temperature information for Temperature sensor 4: normal status.

Wed Mar 13 15:00:00 +0530 [rpsdlxx1: statd: monitor.shelf.fault:alert]: Critical fault reported on disk storage shelf attached to channel 0a. Check fans, power supplies, disks, and temperature sensors.

 

  • STORAGE-FAULT ファンのステータスを表示し CRITICALます。
Fans:
Element Status         Status Bytes  Status Descriptions
1: OK                01,05,16,A7
2: OK                01,04,50,A5
3: CRITICAL          02,01,BC,A1
4: OK                01,04,68,A5
5: OK                01,05,0D,A6
6: OK                01,04,47,A5
7: OK                01,04,74,A5
8: OK                01,04,5C,A5
  • ENVIRONMENT RPMが異常であることを示します。
Cooling Unit installed element list: 1, 2, 3, 4, 5, 6, 7, 8; with error: 3
Cooling Units by element:
[1] 12840 RPM
[2] 11160 RPM
[3] 0 RPM
[4] 11130 RPM
[5] 12990 RPM
[6] 10950 RPM
[7] 11340 RPM
[8] 11160 RPM
  • ファンを再装着しても問題が解決しない

Sign in to view the entire content of this KB article.

New to NetApp?

Learn more about our award-winning Support

NetApp provides no representations or warranties regarding the accuracy or reliability or serviceability of any information or recommendations provided in this publication or with respect to any results that may be obtained by the use of the information or observance of any recommendations provided herein. The information in this document is distributed AS IS and the use of this information or the implementation of any recommendations or techniques herein is a customer's responsibility and depends on the customer's ability to evaluate and integrate them into the customer's operational environment. This document and the information contained herein may be used solely in connection with the NetApp products discussed in this document.